5.6.3. Overview connections
PDU-1 (Main PDU)
•
Independent of PDU-2
•
Max. power consumption 3.600VA
•
Internal protection 2x10A, time lag fuse
•
Total load over all 4 outputs max. 16A
•
Power Strip switchable
•
Energy measurement outlet 1-4
•
Main equipment supply - Electronics
PDU-2
•
Independent of PDU-1
•
Max. power consumption 3.600VA
•
Internal protection 2x10A, time lag fuse
•
Total load over all 4 outputs max. 16A
•
Power Strip switchable
•
Energy measurement outlet 1-4
PDU-1
UPS-Mains connection
(Type C20)
PDU-1, Output 1
Power outlet 1+2
(Type C13, 2.300VA/10A)
PDU-2
UPS-Mains connection
(Type C20)
PDU-2, Output 2
Power outlet 3+4
(Type C13, 2.300VA/10A)
PDU-1, Output 2
Power outlet 3+4
(Type C13, 2.300VA/10A)
PDU-2, Output 1
Power outlet 1+2
(Type C13, 2.300VA/10A)
Installation to front or back#
support rail
Page (04-2015, subject to change) kentix.com36